Power SPD (100KA) equipment

Power SPD (100KA) equipment
Product Detailed
SPD 1, used in the IT, TT, TN-C, TN-S 2,Up:AC385V;Imax:100kA;In:60kA 3.GB18802.1/IEC61643-1 standards. 4,Protection Class B

   NKP-DY-I-100/385/4P

SPD surge arrester /surge protector/surge protective device 100KA 

NKP Power SPD from KEJIA is usually be used in the IT, TT, TN-C, TN-S, TN-C-S and etc power supply system of AC 50/60Hz, rated voltage up to 380V, to protect from direct and indirect lightning impulse and other transient over voltage. As the conditions of IEC61643-1:1998-02 standard, Class I surge protective device, it is category B surge protective device. SPD has two protection modes: MC and MD, SPD is in compliance with GB18802.1/IEC61643-1 standards. 

Functions

protection of heavy-loaded electrical circuits from overloadused to protect not only particular consumers/circuits, but also the whole panelremarkable with high reliability of current characteristicscontrol: automatic switching off at exit failure and recovery after eliminating the danger 

Technical parameter

Model and specification

NKP-DY-I-100/385

No. of poles

4P/3P/2P/1P

Power supply system

TT/TN/IT

Protection grade

B class

 Operation voltage Un(V)

AC220

Max. continuous operating voltage Uc(V)

AC385

Voltage protection level Up(kV)-Less than

2.3

Max. discharging current(8/20 us) Imax(kA)

100

Normal discharging current (8/20 us) In(kA)

60

Status indication

Mechanical flag

Remote contacts

No

Back-up fuse

60A

Response time(ns)

≤25

Ambient temperature

-40°C to +80°C

Relative humidity

On condition that room temperature 30% to 90%

Connection lead cut-area(mm2 )

more than 25

Warning wire cut-area(mm2 )

more than 35

Shell material

PA66

Protection level

IP20

Installation

35mm DIN rail, EN 60715 standards

Test grade

GB18802.1/IEC61643-1 standards

Power SPD (100KA) equipment